GAMATRONIC 1UDC+ Power System -48VDC
The Gamatronic 1U DC+ power system provides clean DC power to sensitive equipment while simultaneously charging the battery bank, and supplying backup power during mains failure.
The 1U DC+ contains a 19” 1 U subrack that can house up to 3 hot-plugged rectifiers, or 2 rectifiers + controller and an LVD device.
Max system capacity: Up to 13 subrack (38 rectifiers + controller), 1266 A with height of 13 U.
Basic shelf: 1U DC+ type I – includes a 19” 1U shelf (subrack) with up to 3 rectifiers.
Electronic Basic shelf:
1U DC +type II – includes a 19” 3U shelf with up to 2 rectifiers + SC
1UDC+ controller and an Electronic LVD device.
Main Features:
• 100A for each 1U shelf
• Intelligent power module, digitally controlled
• One to three hot-swap rectifiers in each shelf
• Active current sharing among rectifiers
• Universal input voltage
• A built-in dual 70 A Electronic Low Voltage Disconnect device (ELVD) for battery protection
• Option to connect 2 external LVD contactors up to 1600 A
• A high-performance, hot-swap system controller (SC 1UDC+) to measure, monitor and control voltages, current, power, battery, temperature, etc.
• USB (SC1U DC+) or TCP/IP+USB communication (SC 1UDC+ NET)
• Temperature compensation enhances battery life
• Battery current limit
• Up to two battery sets handled in one system
• Automatic and pre-programmed battery test (for each battery set)
• Automatic and pre-programmed equalized charging mode
• Comprehensive remote control and monitoring system using a dedicated graphical user interface (GeMSi, PSM-1UDC+)
• Breaking alert by modem (optional)
Tehnički podaci:
MODEL |
48 VDC MODEL |
INPUT | |
Nominal voltage |
185 to 275 VAC |
Permitted variation |
85 to 300 VAC |
Maximum current (at full load)1 |
N*10 A |
Frequency |
47 to 63 Hz |
Power factor (at full load) |
≥ 0.99 |
OUTPUT | |
Maximum configuration |
38 rectifier modules + controller, |
(1255 A, 54 V, 68.4 kW) |
|
Voltage (default) |
54 ±0.2 VDC |
Adjustable range |
47 to 58 VDC |
Regulation (line & load) |
±0.5 %; ±0.25 % with controller |
Nominal Current 1 |
N*33.3 A (Vin>195 VAC) |
N*16 A (Vin=110 VAC) |
|
Ripple&noise @BW=30MHz |
200 mV p-p, 40 mVrms |
Psophometric noise |
-52 dbm over 600 Ώ (<2 mV) |
Efficiency: (nominal load) |
up to 95.2 % |
(50 % load) |
up to 96.2 % |
Overload current 1 |
N*35 A (Vin>200 VAC) |
(Short circuit current, Vo=0) |
<N*20 A (Vin=230 VAC) |
Over-voltage protection |
59.5 V |
Walk-in time |
10 s |
Hold-up time @ nominal input |
20 ms (90% load, |
output decays to 46 V) |
|
Output current indication |
Alpha-numeric LCD on the system controller, 4 LEDs on each module |
Active current sharing |
±10 % accuracy at full load |
GENERAL | |
System controller 2 |
Full status monitoring and communication with a PC, dedicated GUI, USB, RJ47 |
Withstand voltage (1 min) 3 |
3002 VAC INPUT/OUTPUT, 1500 VAC INPUT/GND |
Operating temperature |
-10 to 70 °C (output de-rated at >50 °C by 5 % / °C) |
Humidity |
<95 % non-condensing, equipped with standard PS1UDC+ rack |
Storage temperature |
-20 ~ 80 °C |
EMC |
ETSI, EN 300 386 V1.5.1 (2010-05), EN 55022 Class B, |
Safety |
Conforms to IEC 90652 |
Dimensions: Sub-rack |
19” (W) x 1U (H) x 320 mm (D) w/o terminals (360 mm with terminals) |
Rectifier module |
148 mm (W) x 44 mm (H) x 260 mm (D) |
Weight (kg): Sub-rack 1 |
(N*1.4 kg)+4.2 kg (fully equipped system – max. 11.2 kg) |
Rectifier module |
1.4 kg |
ELVD | |
Max. current withstand |
2×70 ADC or 1×120 AAC |
Notes: |
1. N=number of modules. 2. The basic shelf has a system controller. |
3. Equivalent dc test voltage is applied to overcome Y-capacitors’ leakage current to ground. Output is floating (not grounded) during test. |